According to Consumer, Building and Occupational Services Newsletter - August 2025, CBOS August Newsletter

The most common defect to electrical residential installations is the inadequate fire protection to switchboards.

FXN Rope 

According to Consumer, Building and Occupational Services Newsletter - August 2025, CBOS August Newsletter

The most common defect to electrical residential installations is the inadequate fire protection to switchboards. AS/NZS3000:2018 clause 2.10.7 – prescribes the fire protective measures to prevent the spread of fire from within the switchboards into the building, cavities and conduits. Notes provided under 2.10.7 provide guidance on how this can be achieved.

NOTES:

1 See also Clause 2.10.2.5(h) regarding restricted location of switchboards in or near egress paths or fire exits and Clause 3.9.9 regarding requirements to prevent the spread of fire.

2 There is a very high risk that wiring enclosures, especially those that enter at the top or sides of a switchboard, will contribute to the spread of fire and for this reason care needs to be taken to ensure that these wiring systems are provided with close-fitting entries. In some cases, internal sealing should be provided.

3 An opening with less than 5 mm diameter of free space is considered to be a close fit. Therefore, any opening of 5 mm diameter or greater requires sealing with a fire-retardant sealant.

4 Wiring enclosures, such as conduits, having an internal free space of greater than 5 mm diameter also require sealing to stop any draft effect that could allow the spread of fire.

BCAi Solutions is pleased to present FireXNull as an active extinguisher system using nano technology through either the “sticker” or “rope” applications. BCAi is the approved distributor and technical engineering partner (BCA Engineers) for this product in Australia, Singapore and Malaysia. 

Refer to FireXNull Products: Proactive Fire Prevention Solutions

If you would like to provide additional fire protection measures over and above the requirements of AS/NZS3000-2018 then we would be pleased to assist, please contact .

FXN Rope

FXN Rope

Affix the FXN Rope about 2 to 4 inches below the top edge of the object you're protecting, ensuring it runs parallel.

PFEi Monitor
Text Here
FXN Rope

FXN Rope

Automatic Fire Safety Solution for Enclosures

The FXN Rope series offers an innovative, cost-effective fire suppression solution tailored for electrical enclosures of various sizes. Utilizing advanced nanotechnology, the FXN Rope combines the components of traditional systems into a single product—agent storage, detection, and discharge—ensuring total suppression. Each FXN Rope activates automatically at 220°C (428°F) when exposed to heat, suppressing early-stage fires instantly with an eco-friendly, residue-free clean agent. Designed for reliability and requiring no maintenance, this solution is ideal for protecting high-risk environments containing valuable equipment.

Benefits and Features

Automatic fire suppression
Non-conductive and residue-free
Flexible design for full ignition point coverage
Lightweight, easy to install, and maintenance-free
Cost-effective and environmentally friendly


FXN Rope Applications

Single FXN Rope Sizes Cover Enclosures Up to 70 Cubic Feet (2000 Liters).

  • Electrical cabinets and junction boxes
  • Data centers and server racks
  • Marine and aerospace compartments
  • Industrial equipment and control systems
  • Automotive industry applications
  • Energy Storage System (ESS) enclosures

Its flexible design and advanced technology ensure dependable fire suppression in critical environments.

FXN Rope Models & Coverage Guide

Model No.Rope Size (ft)Rope Size (m)Cabinet Volume (ft³)Cabinet Volume (L)
FXN-R1007.552.32.5 ~ 3.565 ~ 100
FXN-R20010.833.37200
FXN-R30014.764.510300
FXN-R50020.676.317500
FXN-R75027.568.426750
FXN-R100034.4510.5351000
FXN-R150046.5914.2531500
FXN-R200059.3818.1702000

FXN Rope: Fire Suppression in Action

Watch our demo video: a large enclosure equipped with the FXN Rope effectively covers all ignition points. Upon activation, the rope suppresses an early fire in less than 20 seconds.

How It Works

  1. Localized Activation: When a section of the FXN Rope reaches 220°C (428°F), the microcapsules in that area release a clean, non-residue fire-suppressing agent. This agent rapidly vaporizes, absorbing heat and effectively extinguishing the fire without leaving residue or causing damage.
  2. Thermal Propagation: The FXN Rope also contains potassium nitrate, which, upon activation, decomposes exothermically, generating additional heat. This heat propagates along the rope, triggering adjacent microcapsules to release their fire-suppressing agent, ensuring comprehensive suppression throughout the enclosure. 

This combination of localized activation and thermal propagation ensures rapid and effective fire suppression, providing reliable protection for critical environments.


FXN Rope Installation Manual

FXN Rope Installation Instructions  

1. Safety Precautions

  • Ensure the electrical enclosure is completely safe to access, and the electrical power is disconnected before installation.
  • Avoid placing the FXN Rope on a hot surface or in an environment where the ambient temperature exceeds 220°C ± 5°C (428°F ± 9°F).
  • Handle the FXN Rope with care—do not crush, kink, or cut the rope.
  • Wear fireproof gloves when handling the rope to prevent accidental injuries.  

2. Preparation

  • Ensure the surface inside the enclosure is clean, dry, and free of dust, grease, contaminants, or lubricants.
  • Use a lint-free cloth to wipe the surface thoroughly.  

3. Mounting Hook Installation

  • Peel off the protective paper from the adhesive side of the mounting hooks.
  • Press the mounting hooks firmly onto the cleaned surface, ensuring there are no gaps and full adhesion is achieved.
  • Maintain a spacing of 6 inches (150mm) between each hook for optimal support.  

4. Rope Positioning

  • Roll the flat tab of the mounting hooks into a semi-circle to match the rope diameter.
  • Position the FXN Rope horizontally above potential ignition sources for quicker response time.
  • Secure the rope to the mounting hooks using cable ties, ensuring the ties are snug but not overly tight to avoid deforming the rope.  

5. Final Steps

  • Trim any excess length of the cable ties using appropriate cutting tools.
  • Inspect the installation for proper alignment and secure fastening.
  • Label the installation date and 5-year shelf life (expiration) on the enclosure in a visible location.  

6. Maintenance

  • Regularly inspect the FXN Rope and mounting hooks for signs of wear or damage.
  • Replace the FXN Rope every 5 years or immediately after activation.